Annual 90-Minute Emergency Lighting Test & Exit Sign Repairs, Gates NY

Location: Gates, Monroe County, New York
Facility: XPO Logistics distribution center

Project Overview

Our electrical contractor client was contracted to perform the required annual 90-minute emergency lighting test at the XPO Logistics facility in Gates, NY. This inspection is part of routine life-safety compliance for commercial and industrial buildings in Monroe County.

During the full-duration test, three combination emergency/exit light units failed to maintain illumination for the required 90-minute period, triggering corrective action.

Code & Compliance Background – Monroe County, NY

Commercial facilities in Monroe County must comply with the New York State Uniform Fire Prevention and Building Code, as well as nationally recognized life-safety and electrical standards. Emergency lighting systems are required to operate properly in the event of a power outage or other emergency, ensuring a safe building evacuation.

Standard testing requirements include:

  • Monthly functional test (approximately 30 seconds)
  • Annual full-duration battery test (90 minutes)
  • Fixtures must remain illuminated for the entire 90-minute period
  • Testing documentation is maintained for inspection review

For distribution facilities such as XPO Logistics, compliant emergency lighting is critical due to large floor areas, limited natural lighting, active forklift traffic, and multiple shift operations.

Scope of Work Performed

  • Conducted a full 90-minute battery discharge test
  • Verified illumination of all exit signage
  • Inspected charging indicators
  • Evaluated internal battery performance
  • Documented findings for compliance records

Three emergency/exit combination units failed prior to the required duration due to degraded internal batteries.

Corrective Action

The electrician identified the failed units and replaced the internal battery assemblies. Each fixture was then retested to confirm it maintained illumination for the full 90-minute duration. All repairs were documented for compliance with facility records.

Industrial Risk Mitigation

In large industrial environments, emergency lighting failures can create significant evacuation hazards. Routine annual testing helps prevent unexpected fixture failure during emergencies and reduces exposure to fire marshal violations, insurance complications, and liability risks.

Project Outcome

  • Three failed emergency/exit fixtures restored to compliance
  • Full 90-minute performance verified
  • Documentation completed for inspection readiness
  • Facility returned to full life-safety compliance

Conclusion

Annual 90-minute emergency lighting testing is a required life-safety procedure for commercial facilities in Monroe County, NY. This project demonstrates the importance of scheduled inspections and immediate corrective action to maintain code compliance and protect building occupants.

Need annual emergency lighting testing or exit sign repair in Monroe County? Contact our commercial electrical team for documented compliance inspections and service.